Our Products Top > NHA-Type: SMALL and MIDDLE SIZED PACKAGE BOILER |
This NHA-Type Space-saving Package Boiler is suitable to use liquid fuel and gas fuel for industries, hospitals and buildings. The boiler has enabled to be equipped with Low Nox burner, EGR (Exhaust Gas Recirculation) and SI (Steam Injection) for lower Nox emission.
TYPE | 1,200 | 1,500 | 2,000 | 2,500 | 3,000 | 3,500 | 4,000 | 5,000 | 6,000 | |
---|---|---|---|---|---|---|---|---|---|---|
Evaporated Output kg/h | 1,200 | 1,500 | 2,000 | 2,500 | 3,000 | 3,500 | 4,000 | 5,000 | 6,000 | |
Steam Pressure | Max. Operating Pressure MPa(G) | 0.98、1.57、1.96、2.94 | ||||||||
Nor. Operating Pressure MPa(G) | 0.69〜2.75 | |||||||||
Steam Temperature ℃ | Saturate | |||||||||
Boiler Efficiency % | 88、92 | |||||||||
Draft method | Forced Draft | |||||||||
Heating Surface mm² | 19.8 | 22.6 | 30.0 | 36.2 | 42.9 | 49.2 | 59.6 | 66.7 | 86.6 | |
Furnace Volume mm³ | 1.7 | 2.0 | 2.2 | 2.5 | 4.1 | 4.9 | 4.9 | 7.5 | 7.5 | |
Fuel Consumption (M.C.R.) | Heavy Oil kg/h | 90 | 113 | 150 | 188 | 225 | 263 | 300 | 375 | 450 |
City Gas Nmm³/h | 88 | 110 | 147 | 183 | 220 | 257 | 293 | 367 | 440 | |
Boiler Height mm(H) | 2,300 | 2,300 | 2,300 | 2,300 | 2,770 | 2,770 | 2,770 | 3,070 | 3,070 | |
Boiler Width mm(W) | 1,690 | 1,690 | 1,770 | 1,810 | 2,050 | 2,050 | 2,130 | 2,310 | 2,470 | |
Boiler Length mm(L) | 4,450 | 4,680 | 4,910 | 5,140 | 5,350 | 5,735 | 5,805 | 6,315 | 6,315 | |
Min. Boiler Installation Area mm² | 7.52 | 7.91 | 8.69 | 9.3 | 10.97 | 11.76 | 12.36 | 14.59 | 15.6 | |
Net Weight ton | 6.64 | 6.91 | 7.13 | 7.75 | 9.68 | 10.41 | 11.3 | 12.23 | 13.61 | |
Weight with Full Water | At Normal Water Level mm³ | 0.96 | 1.1 | 1.26 | 1.44 | 1.89 | 2.17 | 2.27 | 2.54 | 2.74 |
At Full Water mm³ | 1.2 | 1.36 | 1.55 | 1.77 | 2.5 | 2.88 | 2.97 | 3.32 | 3.52 |
TYPE | 7,000 | 8,000 | 10,000 | 12,000 | 16,000 | 20,000 | 25,000 | 30,000 | |
---|---|---|---|---|---|---|---|---|---|
Evaporated Output kg/h | 7,000 | 8,000 | 10,000 | 12,000 | 16,000 | 20,000 | 25,000 | 30,000 | |
Steam Pressure | Max. Operating Pressure MPa(G) | 0.98、1.57、1.96、2.94 | |||||||
Nor. Operating Pressure MPa(G) | 0.69〜2.75 | ||||||||
Steam Temperature ℃ | Saturate | ||||||||
Boiler Efficiency % | 88、92 | ||||||||
Draft method | Forced Draft | ||||||||
Heating Surface mm² | 101.7 | 105.0 | 134.7 | 165.6 | 208.0 | 267.0 | 343.0 | 400.0 | |
Furnace Volume mm³ | 8.2 | 10.1 | 11.7 | 14.6 | 19.4 | 21.6 | 28.5 | 34.0 | |
Fuel Consumption (M.C.R.) | Heavy Oil kg/h | 526 | 601 | 751 | 901 | 1,201 | 1,501 | 1,877 | 2,252 |
City Gas Nmm³/h | 513 | 587 | 733 | 880 | 1,173 | 1,467 | 1,833 | 2,200 | |
Boiler Height mm(H) | 3,070 | 3,170 | 3,170 | 3,420 | 3,420 | 3,600 | 3,600 | 3,800 | |
Boiler Width mm(W) | 2,580 | 2,580 | 2,660 | 2,660 | 3,150 | 3,200 | 3,600 | 3,630 | |
Boiler Length mm(L) | 6,695 | 6,980 | 7,590 | 8,130 | 9,145 | 10,260 | 10,960 | 12,650 | |
Min. Boiler Installation Area mm² | 17.27 | 18.01 | 20.19 | 21.63 | 28.81 | 32.83 | 39.46 | 45.92 | |
Net Weight ton | 14.76 | 17.5 | 19.55 | 22.22 | 24.61 | 27.46 | 32.0 | 45.0 | |
Weight with Full Water | At Normal Water Level mm³ | 3.08 | 3.24 | 3.81 | 4.33 | 6.22 | 7.2 | 8.1 | 10.1 |
At Full Water mm³ | 3.91 | 4.15 | 4.85 | 5.49 | 8.39 | 9.6 | 10.5 | 12.5 |
NHA-Type boiler has a simple construction which consists of convection zone of the vertically connected tubes to spacious upper and lower drums and a combustion chamber covered with shape bent tubes installed at the side of this zone.
Staggered arrangement of the tubes is employed at convection zone to obtain best heat absorption letting gas pass in a single passage method. The tubes at convection zone can be easily inspected by removing them temporarily for the wall separating convection zone from furnace is made of demountable fire bricks inserted between water tubes.
The tubes forming a combustion chamber side walls are bent on such a large radius that tube cleaners can easily pass through the tubes. Tubes outside cleaning can be conducted by soot blower even during boiler operation and when stopping water washing can be also conducted. In addition to these merits this type of boiler as also a suitable construction for pressurized burning for fin tubes are employed for the front, rear and side walls, around which double casing are installed to prevent gas leakage.
That the associated equipment except feed water tank and water softening equipment are all shop assembled makes boiler operation very easy.
Gas fuels such as LNG, LPG and City gas are all available for this type of boiler by selection of each suitable burner.